Application: | 3pH AC Power with Voltage Below 660V and 50Hz |
---|---|
Function: | Digital Energy Feedback |
Brand: | V&T |
Still deciding? Get samples of US$ 50/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input Voltage | |
Power Voltage |
3AC220V,3AC380V,3AC660V(-15%+10%)or customized |
Grid frequency |
50±3Hz |
DC Voltage |
220V<400V;380V:<720V;660V:<1150V |
Voltage harmonics |
<5% |
Performance characteristics | |
Rated capacity |
220V: 30KW/45KW/75KW/110KW 380V: 45KW/75KW/110KW/160KW/200KW/250KW/315KW/400KW/500KW/600KW 660V: 45KW/75KW/110KW/160KW/200KW/250KW/320KW/400KW/500KW/600KW |
DC voltage control |
Feedback function: Operating voltage:>1.5 times the grid voltage+50V 220V:<400V 380V:<720V 660V:<1150V PWM rectification and SVG features: Stable voltage:>1.5times the grid voltage+50V 220V:<400V 380V:<720V 660V:<1150V |
Voltage control accuracy |
≤0.5% |
Power factor |
>0.95 |
Output harmonic content |
<5% |
Overoad capacity record |
1.45 times for 60 seconds 1.5 times protection |
Operating effidency |
≥97% |
Full response time |
≤10ms |
Control mode | |
Control Chip |
150MHz high-speed DSP digitalsignal proce ssor Programmable gate anray FPGA |
Control method |
PWM curent tracking control technology DC side voltage balance control technology; Coordinate transfomation vector control technology,Instantaneous current detection technology |
Control function |
Feedback control PWM rectification control Static varcompensation control (SVG) |
Operation mode |
Resistive load;Capacitive load;inductive load |
Communicationmethod Monitor interface |
CAN,RS485 display: Grid voltage,ACcurent,DC voltage,real-time power,feedback energy,faultinfomation and waming status,etc Settings: Control parameters such as feedback input voltage,feedback cutoff voltage,DCconstant voltage,feedback voltage,working mode,etc |
Protection me thod |
Overcurrent DC overvoltage,AC overvoltage,AC undervoltage,IGBT direc connection, equipment overmeating,reactor overheating,phase-locked fault and extemal settings |
Protection response time |
Less than 300us,the overcurrent,overvoltage and IGBT through protection are less than 10us |
Fault output |
Relay output,2 nomally open passive contacs,contact capacity AC250V/5A |
Cooling method |
Controllable air cooling |
Control power |
220VAC |
LCD Product Specifications