After-sales Service: | Yes |
---|---|
Warranty: | 18 Months |
Phase: | Three |
Still deciding? Get samples of US$ 50/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Safe&Reliable
IP65 protection, aluminum housing, built-in lightning protection, high-precision leakage protection
Friendly&Flexible
Integrated PV and storage system modem
Support full power discharge, automatic management of battery charge and discharge
Wide PV and battery voltage input range
Support multiple parallel connections
Economical&Practical
It is more economical to support multiple operating modes
Can be as a UPS for the important loads when power off
Support intelligent EMS management function
Support on/off-grid automatic switching function to ensure uninterrupted power when important loads are off-grid
Model | VTE30K-GS | VTE40K-GS | VTE50K-GS | VTE60K-GS |
DC Input | ||||
Max. power(KW) | 36KW | 48KW | 60KW | 72KW |
Max. DC voltage (V) | 1000V | |||
MPPT voltage range(V) | 180V-900V/630V | |||
MPPT operating voltage range at rated power(V) | 300V-900V | 400V-900V | 400V-900V | 450V-900V |
MPPT tracker/strings | 2/2/2 | 2/2/2 | 2/2/2/2 | 2/2/2/2 |
Max.input current of single MPPT(A) | 36A*3 | 36A*3 | 36A*4 | 36A*4 |
Short-circuit current of PV input(A) | 42A/42A/42A | 42A/42A/42A | 42A/42A/42A/42A | 42A/42A/42A/42A |
AC output | ||||
Rated output power(KW) | 30KW | 40KW | 50KW | 60KW |
Max. Apparent AC power(KVA) | 30KVA | 40KVA | 50KVA | 60KVA |
Max. output current(A) | 45A | 60A | 75A | 87A |
Grid voltage/range(V) | 400V,3L+N+PE | |||
Frequency (HZ) | 50/60HZ | |||
PF | 1(0.8lagging-0.8leading | |||
THDI | <3% |
Battery voltage range(V) | 220V~800V | |||
Max. input/output voltage(V) | 800V | |||
Rated charge/discharge current(A) | 100A | 100A | 100A | 100A |
Max. input/output power(KW) | 30KW | 40KW | 50KW | 60KW |
Battery type | lithium /Lead-acid | |||
Communication interface | CAN/RS485 |
Rated output power(KW) | 30KW | 40KW | 50KW | 60KW |
Max. Apparent AC power(KVA) | 30KV A | 40KV A | 50KV A | 60KV A |
Max. single-phase apparent output power(KVA) | 10KV A | 13KV A | 17KV A | 20KV A |
Rated output voltage(V) | 400V,3L+N+PE | |||
Rated output current(A) | 45A | 60A | 75A | 87A |
Rated frequency (HZ) | 50/60HZ | |||
Automatic switching time (MS) | <10ms | |||
THDU | <3% | |||
Overload capacity | 110%,30S/120%,10S/150%,0.02S |
AC over-current protection | yes |
Ground fault detection protection | yes |
Power grid monitoring protection | yes |
Residual current detection protection | yes |
General Data | |
Euro Efficiency | >98.2% |
Protection class | IP54 |
Noise Emission (Typical) | <40dB |
Operation Temperature | -25~+60ºC |
Cooling | Intelligent Fan |
Relative Humidity | 5~90% (non-condensing) |
Altitude | 4000m(>2,000 De rating) |
Dimensions (W/D/H) MM | 800*600*280MM |
Weight(KG) | 50KG |
Inverter Topology | transformer less |
Self-Consumption | <1W |
Display and communication | |
Display | LCD |
Interface :RS485/WiFi/GPRS | yes/opt/opt |